Safety first. Always switch off, lock out and tag the supply before touching a motor. Discharge capacitors. Test only with a qualified person and the right instruments.
Most motor failures can be traced to a small number of root causes. The flow is: see the symptom, find the root cause, apply the fix, and stop it from coming back. Use the table below as a quick guide, then read the detail for each fault.
Quick table: symptom to likely cause
| Symptom | Likely causes | First check |
|---|---|---|
| Motor too hot | Overload, voltage problem, poor cooling | Current on 3 phases, voltage, fan and air path |
| Hum, no start | Single phasing, jam, bad capacitor | All three phases at the terminals |
| Trips on overload | Overload, low voltage, wrong relay setting | Running current vs nameplate and relay setting |
| Vibration | Unbalance, misalignment, loose base, bearings | Vibration at 1x rpm vs 2x rpm; alignment |
| Noise | Bearings, rubbing, electromagnetic noise, fan | Listen with and without load; check air gap |
| Low insulation reading | Moisture, dirt, ageing, overheating | Megger test, dry and clean, retest |
Motor overheating: causes and fixes
- Overload. Compare running current with the nameplate current. Fix: reduce the load or use a larger motor.
- Low or high voltage. More than +/-10 percent voltage variation causes extra heating. Fix: correct the supply, or use a motor suited for it.
- Voltage unbalance. A small unbalance in voltage gives a large current imbalance and extra heat. Fix the supply or loose connections.
- Poor cooling. Dust-blocked fins, broken fan, covered air inlet, or high ambient temperature. Fix: clean, repair the fan, improve ventilation.
- Too many starts or heavy inertia loads. Fix: limit the starts per hour, use a soft starter or VFD, or choose a motor with a suitable duty rating.
- VFD operation at low speed with a self-cooled fan. Fix: use a separate cooling fan or a motor designed for VFD duty.
Rule of thumb: for every 10 C of extra temperature, insulation life roughly halves. So even a small heat reduction increases the motor life a lot.
Burnt winding: how to read the cause
- One phase burnt: single phasing.
- All phases burnt evenly: overload, low voltage or poor cooling.
- Burnt at the slot ends or coil heads: poor impregnation, loose coils or contamination.
- Turn-to-turn short (a small burnt spot): damaged wire during winding, vibration or a voltage spike.
- Phase-to-phase burn: insulation failure between phases at the end winding.
Before restarting a replaced or rewound motor, find and remove the root cause. Otherwise the new winding will fail again.
Motor bearing failure: causes
- Wrong or too much grease, or mixing incompatible greases.
- No grease, or old grease (re-greasing interval missed).
- Misalignment or belt over-tension that loads the bearing.
- Shaft current from a VFD (see below).
- Dust, water or contamination getting in through damaged seals.
- High vibration from outside, or rough handling before installation.
Early signs are a rising noise, a rising temperature and a rise in vibration. Trend them every month to catch failure before the motor stops.
Motor humming but not starting
- Isolate the supply and turn the shaft by hand. If it is stuck, check the load and bearings.
- Check all three phases at the motor terminals. A missing phase is the most common reason for a 3 phase motor.
- For a single phase motor, check the starting capacitor and the centrifugal switch or relay.
- Check for wrong connection (star/delta) and loose terminals.
- Check for a broken rotor bar in older motors (the motor may hum and run slowly or fail to start).
Motor tripping on overload
First measure the running current on all three phases. If the current is higher than the nameplate, the load or the supply is the problem. If the current is normal, the overload relay may be set too low, or may be old. Set the relay to the nameplate full load current (and service factor if applicable). Check also for loose connections that cause nuisance trips.
Motor vibration and noise: causes
| Vibration at | Likely cause |
|---|---|
| 1 x running speed | Unbalance, bent shaft, loose parts |
| 2 x running speed | Misalignment or looseness |
| 2 x line frequency (100 Hz at 50 Hz supply) | Electrical: stator/rotor eccentricity, broken rotor bar, voltage unbalance |
| High frequency, grinding sound | Bearing defect |
Noise sources can be mechanical (bearings, fan, rubbing), aerodynamic (fan, ventilation) or electromagnetic (slot-pole choice, air-gap, supply harmonics from a VFD). Use a vibration meter and compare with the standard limit for your motor size.
Single phasing of a three phase motor
When one supply line is lost, the motor current in the other two phases rises sharply, often 1.7 times or more, and the winding heats up fast. Protect with a phase failure relay or an overload relay with phase-loss protection, check fuses and contactors, and check terminals for looseness. A single phased winding usually shows one or two phases burnt, with the third normal.
Motor insulation breakdown
Insulation ages with heat, moisture, dirt, oil, chemicals and voltage spikes. Test with a megger (insulation resistance, IR) and, for important motors, a polarisation index (PI). A low reading often improves after drying and cleaning. If not, rewinding or replacement is needed. For VFD fed motors, use inverter-duty insulation to withstand fast voltage spikes.
Motor current imbalance
If the currents in the three phases differ by more than about 10 percent, find the cause. Possible causes: unbalanced supply voltage, loose or corroded connections, a shorted turn in the winding, or a bad contactor. Rotate the supply connections on the motor; if the high-current phase follows the supply, the problem is on the supply side, and if it stays with the motor terminal, the problem is in the motor.
VFD fed motor and bearing currents
A VFD makes a high-frequency common-mode voltage that can send small currents through the bearings. This creates tiny pits (called fluting) and early bearing failure. Remedies include an insulated bearing (usually on the non-drive end), a shaft grounding ring, a properly bonded and shielded motor cable, a lower switching frequency, and output filters where needed.
Motor rewinding vs replacement
- Rewind when the motor is large, costly or special, the core is good, and a quality shop does it with the right wire and varnish. Poor rewinding can reduce efficiency by one or two percent or more.
- Replace when the motor is small, old or low efficiency and runs long hours, or when the repair cost is more than about half the price of a new motor. An IE3 motor can repay its extra cost through lower electricity bills. See the IE class guide.
Related: how motors are made, motor design calculations, glossary.
Common questions
Why is my motor getting too hot?
The common causes are overload, low or high supply voltage, voltage unbalance between phases, blocked cooling air or a broken fan, high ambient temperature, too many starts, bad bearings, and winding faults. Measure the current on all three phases first, and compare with the nameplate.
Why does a motor hum but not start?
Humming without rotation usually means the motor is not getting all three phases (single phasing), the rotor is jammed or the load is too heavy, the bearings are seized, or, in a single phase motor, the starting capacitor or centrifugal switch has failed.
What causes winding burnout?
Heat is the cause. Heat comes from overload, single phasing, low voltage, frequent starts, poor cooling, moisture and contamination, or insulation ageing. A burnt winding pattern helps find the root cause: one phase burnt means single phasing; all phases burnt evenly means overload.
What is single phasing?
It is when one of the three supply lines is lost (for example a blown fuse). The motor keeps running on two phases at a higher current, or hums if stopped. Without proper overload and phase failure protection, the winding burns in minutes.
Should I rewind or replace a motor?
For large motors, rewinding by a good shop can restore the motor nearly to its original state. For small motors, or for old low-efficiency motors that run many hours, a new IE3 motor often pays back through electricity savings. Compare the repair cost, the lost efficiency risk and the energy bill.
What is a safe insulation resistance value?
A common minimum for low voltage motors is 1 megohm, and healthy windings read much higher. Many plants use the rule of about 1 megohm per kV of rated voltage plus 1 megohm, and trend the readings over time. Test with a megger with the motor isolated. Follow the standard that applies at your site.