Electric Motor Troubleshooting Guide: Causes and Fixes

Symptom, root cause and fix for the most common motor problems. Short, practical and safe.

Safety first. Always switch off, lock out and tag the supply before touching a motor. Discharge capacitors. Test only with a qualified person and the right instruments.

Most motor failures can be traced to a small number of root causes. The flow is: see the symptom, find the root cause, apply the fix, and stop it from coming back. Use the table below as a quick guide, then read the detail for each fault.

Quick table: symptom to likely cause

SymptomLikely causesFirst check
Motor too hotOverload, voltage problem, poor coolingCurrent on 3 phases, voltage, fan and air path
Hum, no startSingle phasing, jam, bad capacitorAll three phases at the terminals
Trips on overloadOverload, low voltage, wrong relay settingRunning current vs nameplate and relay setting
VibrationUnbalance, misalignment, loose base, bearingsVibration at 1x rpm vs 2x rpm; alignment
NoiseBearings, rubbing, electromagnetic noise, fanListen with and without load; check air gap
Low insulation readingMoisture, dirt, ageing, overheatingMegger test, dry and clean, retest

Motor overheating: causes and fixes

Rule of thumb: for every 10 C of extra temperature, insulation life roughly halves. So even a small heat reduction increases the motor life a lot.

Burnt winding: how to read the cause

Before restarting a replaced or rewound motor, find and remove the root cause. Otherwise the new winding will fail again.

Motor bearing failure: causes

Early signs are a rising noise, a rising temperature and a rise in vibration. Trend them every month to catch failure before the motor stops.

Motor humming but not starting

  1. Isolate the supply and turn the shaft by hand. If it is stuck, check the load and bearings.
  2. Check all three phases at the motor terminals. A missing phase is the most common reason for a 3 phase motor.
  3. For a single phase motor, check the starting capacitor and the centrifugal switch or relay.
  4. Check for wrong connection (star/delta) and loose terminals.
  5. Check for a broken rotor bar in older motors (the motor may hum and run slowly or fail to start).

Motor tripping on overload

First measure the running current on all three phases. If the current is higher than the nameplate, the load or the supply is the problem. If the current is normal, the overload relay may be set too low, or may be old. Set the relay to the nameplate full load current (and service factor if applicable). Check also for loose connections that cause nuisance trips.

Motor vibration and noise: causes

Vibration atLikely cause
1 x running speedUnbalance, bent shaft, loose parts
2 x running speedMisalignment or looseness
2 x line frequency (100 Hz at 50 Hz supply)Electrical: stator/rotor eccentricity, broken rotor bar, voltage unbalance
High frequency, grinding soundBearing defect

Noise sources can be mechanical (bearings, fan, rubbing), aerodynamic (fan, ventilation) or electromagnetic (slot-pole choice, air-gap, supply harmonics from a VFD). Use a vibration meter and compare with the standard limit for your motor size.

Single phasing of a three phase motor

When one supply line is lost, the motor current in the other two phases rises sharply, often 1.7 times or more, and the winding heats up fast. Protect with a phase failure relay or an overload relay with phase-loss protection, check fuses and contactors, and check terminals for looseness. A single phased winding usually shows one or two phases burnt, with the third normal.

Motor insulation breakdown

Insulation ages with heat, moisture, dirt, oil, chemicals and voltage spikes. Test with a megger (insulation resistance, IR) and, for important motors, a polarisation index (PI). A low reading often improves after drying and cleaning. If not, rewinding or replacement is needed. For VFD fed motors, use inverter-duty insulation to withstand fast voltage spikes.

Motor current imbalance

If the currents in the three phases differ by more than about 10 percent, find the cause. Possible causes: unbalanced supply voltage, loose or corroded connections, a shorted turn in the winding, or a bad contactor. Rotate the supply connections on the motor; if the high-current phase follows the supply, the problem is on the supply side, and if it stays with the motor terminal, the problem is in the motor.

VFD fed motor and bearing currents

A VFD makes a high-frequency common-mode voltage that can send small currents through the bearings. This creates tiny pits (called fluting) and early bearing failure. Remedies include an insulated bearing (usually on the non-drive end), a shaft grounding ring, a properly bonded and shielded motor cable, a lower switching frequency, and output filters where needed.

Motor rewinding vs replacement

Related: how motors are made, motor design calculations, glossary.

Common questions

Why is my motor getting too hot?

The common causes are overload, low or high supply voltage, voltage unbalance between phases, blocked cooling air or a broken fan, high ambient temperature, too many starts, bad bearings, and winding faults. Measure the current on all three phases first, and compare with the nameplate.

Why does a motor hum but not start?

Humming without rotation usually means the motor is not getting all three phases (single phasing), the rotor is jammed or the load is too heavy, the bearings are seized, or, in a single phase motor, the starting capacitor or centrifugal switch has failed.

What causes winding burnout?

Heat is the cause. Heat comes from overload, single phasing, low voltage, frequent starts, poor cooling, moisture and contamination, or insulation ageing. A burnt winding pattern helps find the root cause: one phase burnt means single phasing; all phases burnt evenly means overload.

What is single phasing?

It is when one of the three supply lines is lost (for example a blown fuse). The motor keeps running on two phases at a higher current, or hums if stopped. Without proper overload and phase failure protection, the winding burns in minutes.

Should I rewind or replace a motor?

For large motors, rewinding by a good shop can restore the motor nearly to its original state. For small motors, or for old low-efficiency motors that run many hours, a new IE3 motor often pays back through electricity savings. Compare the repair cost, the lost efficiency risk and the energy bill.

What is a safe insulation resistance value?

A common minimum for low voltage motors is 1 megohm, and healthy windings read much higher. Many plants use the rule of about 1 megohm per kV of rated voltage plus 1 megohm, and trend the readings over time. Test with a megger with the motor isolated. Follow the standard that applies at your site.

Information here is for learning. For design, purchase or legal decisions, check the latest BIS, BEE and IEC standards and your motor maker's data sheet.